Comment on What's Wrong with AI?parentComments−quickthrowman4moI’d like to see some evidence of that, adding evaporative cooling towers to a chilled water loop can almost double the COP. I don’t see datacenter operators foregoing much cheaper opex unless they’re in a water-critical area.